C3645-W
Easy to use Conductivity Controller
Easy to use Conductivity Controller with Set-point Relay
The Model C3645-W Conductivity Controller is designed to be as easy to use as possible without compromising on accuracy.
When paired with a good quality insertion conductivity cell or dip mounting conductivity cell, the C3645 will display precision conductivity measurements in either µS (micro-siemens) or mS (milli-siemens).
Available in a surface mounting enclosure or as a Din-Rail mounted unit for mounting on the back plate of a control panel.
The C3645-W easy to use Conductivity controller has a large easy to read LCD display giving good visibility of the current conductivity value to an operator.
The C3645-W can be powered from either 115 VAC or 230 VAC 50/60Hz.
C3645-W Conductivity Ranges
The C3645-W is available in with the following ranges:-
Cell Constant | Range 1 | Resolution 1 | Range 2 | Resolution 2 | Range 3 | Resolution 3 |
---|---|---|---|---|---|---|
K = 0.01 | 0 - 2.000µS | 0.001µS | 0 - 20.00µS | 0.01µS | 0 - 200.0µS | 0.1µS |
K = 0.1 | 0 - 20.00µS | 0.01µS | 0 - 200.0µS | 0.1µS | 0 - 2000µS | 1µS |
K = 1.0 | 0 - 200.0µS | 0.1µS | 0 - 2000µS | 1µS | 0 - 20.00mS | 0.01mS |
K = 10.0 | 0 - 2000µS | 1µS | 0 - 20.00mS | 0.01µS | 0 - 200.0mS | 0.1mS |
The C3645-W will work with any good quality AWE conductivity cell instruments from our K=0.01, K=0.1, K=1.0 and K=10.0 cell constants.
When the C3645 is provided in Din Rail mounting configuration, it measures just 105mm wide x 100mm high x 58mm deep. When supplied in the surface mounting enclosure the unit measures 135mm wide x 170mm high and 115mm deep.
When in surface mounting configuration, the conductivity controller has a clear door for easy access to the simple to use controls, allowing the operator to calibrate the instrument or set the two set points from the front panel.
The value of the set-point is easy to determine using the front mounted potentiometers. By selecting a value at which the set-point should operate and either a high or low level operation to engage the set-point.
C3645-W Simple Conductivity Controller with Automatic Temperature Compensation
To ensure that the C3645-W is providing precision measurements in environments with fluctuating temperatures, the C3645-W works with a conductivity cell with integrated temperature compensation. The measured conductivity value is automatically compensated for with a factor of 2% per ºC from a base of 20.
The temperature compensation operates from a value of 0-100ºC across the full measured range of the conductivity controller.
C3645-W easy to use Conductivity Controller with Set-point with On/Off Control Relay.
The C3645-W has an easy to programme on/off control set point with an adjustable time delay of up to 40 seconds before the relay operates. The relay co-operation can be selected for either high or low operation, via the means of a control switch.
When the setpoint is configured for use under low operation, then when the monitored Conductivity value is lower than the set-point value, the LED is lit and the corresponding relay is activated. If the relay has the delay function activated, then the timer will be called until the relay is activated.
The C3645 is designed for use under high operation, then when the monitored Conductivity value is higher than the setpoint, the LED is lit and the corresponding relay is activated. Again, if a delay has been assigned to the relay, then the relay will wait until this delay has expired before activating the relay.
As the C3645-W is an easy to use conductivity controller with excellent control options, it makes an excellent choice as a cost effective conductivity controller for many processes including rinse water control, conductivity controlled bleed or system purge, water treatment processes and solution strength control.
C3645-W easy to use Conductivity Controller with 4-20mA output
The C3645-W easy to use conductivity controller has an industry standard 4-20mA output isolated to 500Ω. This 4-20mA output can be used with a variety of control equipment including PLC's and Chart Recorders. The 4-20mA output in this instrument is non-expandable meaning that the current output is not suitable for use with proportional control dosing pumps, but does correspond precisely to the measured range of the instrument selected.
C3645-W Controller Specifications
-
Specifications
Model No:- C3645-W
Conductivity Ranges:- From 0 - 2.000µS to 0 - 200.0mS dependent on cell constant.
Supported Cell Constants:- K=0.01, K=0.1, K=1.0, K=10.0
Temp. Compensation:- 2% per ºC
Temp. Range:- 0ºC to 100ºC
Set Points:- 1 On / Off, High / Low selectable, 2 amp inductive
Action:- On/Off over 100% of range
Time Delay:- 0-40 seconds adjustable
Current output:- 0-20/ 4-20mA isolated into 500Ω
Zero:- ±15%
Slope:- ±20%
Mains Supply:- 230 Volt / 115 Volt, 50 / 60Hz.
Weight:- 265 grams DIN version
Dimensions:- 100 x 105 x 58mm
-
Features
- Easy to use precision conductivity controller with set point for on / off control, complete with delay timer.
- Din rail mounting or surface mounting in a compact enclosure with makalon access door.
- Easy calibration procedure even for untrained operators with adjustment of Zero and Span via front mounted potentiometers.
- Clear crisp display so the conductivity value, set-point setup and calibration procedure can be easily checked and adjusted as required.
- Isolated 4-20mA output for easy integration with a digital chart recorder, PLC or online data logger
-
Data Sheets